Air and Water Flow Rate Optimisation For a Fan Coil Unit in Heat Pump Applications

Files in This Item:
File Description SizeFormat 
D Finn 2012 Edwards and Finn (Purdue #3497) done.pdf4.51 MBAdobe PDFDownload
Title: Air and Water Flow Rate Optimisation For a Fan Coil Unit in Heat Pump Applications
Authors: Edwards, Killian C.
Finn, Donal
Permanent link: http://hdl.handle.net/10197/4625
Date: 2012
Abstract: The degradation in efficiency of auxiliary components in heating/cooling systems when operating at part load is frequently reported. Through the use of variable speed components, the supplied capacity can be reduced to match the required load and hence reduce unnecessary energy consumption. However, for fan coil units, difficulties can arisewhen optimizing fan and pump speeds at part load. Practicallylocating optimal water and air flowrates from readily available information and for varying supplied capacities is necessary,in order to reduce the fan coil power consumption. This research attempts to identify whether optimal fan and pump speeds exist for a fan coil unit and how they can be implemented, in a practical manner, in a system control applications. Using an empirical fan coil and pump model, the total power consumption (fan and pump) for different combinations of fan and pump speeds over a range of capacities was calculated. It was observed that, for a given capacity, an optimal combination of fan and pump speeds exists and there was a significant change in power consumption for different combinations of fan and pump speeds supplying the same capacity. A control strategy is described that utilizes a simple fan coil capacity estimation model, coupled with air and water flowrates, along with nominal design data. The pump speed is optimized using PID control to maintain the space temperature at the chosen set-point, which matches the supplied capacity to the required capacity. At set-time intervals, the capacity estimation model is utilized to optimize the water and air flowrates for the required capacity. The control strategy is evaluated, using a full building simulation model for a daily load profile and is compared to two baseline conditions: for no control of the fancoils/pump combination and for PID circulation control of the pump only. The optimal fan and pump speed control resulted in a 43% and 24% decrease in power consumption with compared to the no control baseline and the PID controlled circulation pump strategy, respectively.
Type of material: Conference Publication
Publisher: Purdue University
Copyright (published version): 2012 the authors
Keywords: Air flow;Water flow;Coil unit;Heat pump applications
Language: en
Status of Item: Not peer reviewed
Conference Details: International High Performance Buildings Conference at Purdue, July 16-19, 2012
Appears in Collections:Mechanical & Materials Engineering Research Collection

Show full item record

Google ScholarTM

Check


This item is available under the Attribution-NonCommercial-NoDerivs 3.0 Ireland. No item may be reproduced for commercial purposes. For other possible restrictions on use please refer to the publisher's URL where this is made available, or to notes contained in the item itself. Other terms may apply.