Chen, JunruJunruChenMilano, FedericoFedericoMilanoO'Donnell, TerenceTerenceO'Donnell2020-08-182020-08-182019 IEEE2019-09IEEE Transactions on Power Systems0885-8950http://hdl.handle.net/10197/11485This letter applies voltage stability analysis to grid feeding converters in the presence of the converter stability versus the grid state and its operation. By applying this analysis, it is shown that the converter may become unstable if the converter reference power or current exceeds the line capacity. This letter proposes to use a conventional PV curve to determine the stability of the dynamic response of grid-feeding converters considering both power and current limits.en© 2019 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.Current limitGrid-feeding converterReactive power compensationStability criterionVoltage stabilityAssessment of Grid-Feeding Converter Voltage StabilityJournal Article3453980398210.1109/TPWRS.2019.29205162019-12-1715/SPP/E3125https://creativecommons.org/licenses/by-nc-nd/3.0/ie/